Bigger Is
Not Better:
Sizing Air
Conditioners Properly
How
They Size Air Conditioning Systems in Florida
Sizing
Air Conditioners: Recommendations for Contractors
It is generally accepted that
"the right way" to specify an air
conditioning system is to calculate the loads and
select a piece of equipment that will provide
comfort to the customer in a wide variety of
conditions. Unfortunately this is rarely
practiced.
A colleague
of ours (we will call him Bill) approached us at
a conference seeking advice on selecting an air
conditioner for his renovated home. Our
recommendations included, "Be sure that the
cooling load is calculated and that the air
conditioner is sized to that load." When
Bill attempted to follow these instructions, only
one of the four contractors would submit a sizing
calculation (two others just wanted to know how
many square feet there were in the house).
Bill hired
the contractor who did the calculation and
installed a high-efficiency four-ton unit. Is
this a success story? Not really. The contractor
calculated a total cooling load of 37,580 BTUs
per hour at 105 degrees F outside and 70 degrees
F inside. While the cooling load he calculated
could have been met by a three-and-a-half ton air
conditioner, the contractor convinced Bill to buy
a four-ton unit "because then you will
always have plenty of cooling."
Bill's air
conditioner short-cycles (runs for shorter
periods of time than it should) even during the
hottest weather and removes very little moisture
from the air. What went wrong? Four things:
- The design temperature for
the area is 97 degrees F. The contractor
increased the outside design temperature
by 8 degrees F.
- The recommended design
indoor temperature is 75 degrees F. The
indoor temperature was lowered by 5
degrees F. The temperature
"fudges" increased the inside
to outside differential by 59%.
- The contractor increased the
calculated load by 20% as a safety
factor.
- The equipment selected was a
half-ton larger than the next highest
available size to meet the load he
calculated.
A
two-and-a-half ton air conditioner would have
been perfect for Bill's house. Instead he
paid more for an extra one-and-a-half tons of
cooling. In addition to costing more to buy,
Bill's air conditioner will use more energy than
a properly sized system, raising his utility
bills. It won't dehumidify the air as well as a
smaller system would, and chances are that Bill
will be less comfortable. The utility, which gave
Bill a rebate for his purchase, will also lose,
since the oversized unit aggravates summer
peak-load requirements.
Selecting
the Right AirConditioner for the Job
Before one
can design an efficient and effective air
conditioning system, the load must first be
calculated using established techniques. The Air
Conditioning Contractors of America (ACCA)
conducted an industry study of residential
cooling load calculations and developed Manual J
to estimate these loads. Manual J was
adopted by ACCA and the Air-Conditioning and
Refrigeration Institute (ARI), and is the
standard method of sizing loads for residences.
ACCA has also produced Manual S for
selecting equipment and Manual D for duct design
(revised in January 1995). Manual S provides a
method to select air conditioners based on the
estimated sensible and latent load calculated for
the particular house in the local climate.
If mistakes are made in the load
calculations or the sizing method is flawed or
incorrect inputs are used, the equipment will be
incorrectly sized and will not perform as it
should. Field studies have shown that most
equipment is substantially oversized compared to
Manual J specifications. Studies found that
53% of the air conditioners checked were a ton
(12,000 Btu/h) or more oversized and a found
a third of the air conditioners to be a ton or
more oversized.
What is
"Proper" AC Sizing?
A properly
sized air conditioner should provide maximum
value to the customer as well as a reasonable
profit and further customer referrals for the
contractor. If an air conditioner is cycling even
at four in the afternoon on the hottest days, it
is a sure sign it is oversized. Incidentally, if
the air conditioner is running continuously on
hot days, it doesn't necessarily mean that it is
the right size. It is more likely that the system
is oversized and has one of three big problems:
leaky ducts, improper charge, or low air flow
across the coil.
Oversizing:
Causes and Effects
Customers
depend on the expertise of contractors in
selecting air conditioners. Yet contractors
generally size air conditioners at least a
half-ton larger than necessary and often oversize
by a ton or more. Even the most conscientious
contractor is driven to avoid call-backs (or even
lawsuits). An oversized air conditioner can mask
problems from duct leaks, improper flow across
the coils, and improper charge.
Unfortunately,
many customers think that "bigger is
better," so in a competitive situation, the
contractor proposing the proper size unit may
lose the bid. Contractors are hesitant to adopt
an unfamiliar method of sizing when the methods
they have developed over the years have served
them well: "I've done it this way for 30
years and I've never had a complaint."
It is no
surprise then that air conditioners are
oversized; however, the advantages of a properly
sized air conditioner are so large that these
barriers need to be overcome. Customers pay a
price for oversized air conditioners, and in many
climates, lose comfort as well.
A properly
sized air conditioner costs the customer less
(see Figure 1). Bill's air conditioner cost him
more money because it was too big. The contractor
had the opportunity to discuss the value of the
air conditioner based on the delivered efficiency
and offer Bill equipment at a lower cost. He
missed the opportunity.
Short Cycles
Air
conditioners are very inefficient when they first
start operation. It is far better for the air
conditioner to run longer cycles than shorter
ones. The efficiency of the typical air
conditioner increases the longer it runs.
Figure 2
illustrates that if the on-time of an air
conditioner is only 5 minutes the efficiency
(EER) is 6.2. If a properly sized air conditioner
half the size were used instead, the same amount
of cooling would take place in about 9 minutes,
and the efficiency would rise to 6.9. This
represents a savings of 10% for the customer.
Most of the
cooling season the cooling loads are well below
the capacity of properly sized air conditioners,
and for oversized units the short cycling is a
substantial problem. Because of the short cycles,
Bill's high-efficiency air conditioner is less
efficient.
Moisture
Buildup
The ability of
the air conditioner to remove moisture (latent
capacity) is lowest at the beginning of the air
conditioner cycle. The moisture removed from the
indoor air is dependent upon the indoor coil
temperature being below the dew-point temperature
of the air. The moisture then wets the indoor
coil and, should the unit run long enough, will
begin to flow off the coil and be removed out of
the condensate drain.
For short
cycles, the coil does not have time to operate at
the low temperature and when the unit stops, the
moisture on the coil evaporates back into the
indoor air. Thus, in humid climates, a properly
sized air conditioner will do a far better job of
removing moisture from the air than oversized
units. Bill's oversized air conditioner could not
remove enough moisture from the air, so his house
was cold and clammy.
Noisy Operation
The speed of
the air blowing through the supply registers and
the air being drawn into the return grille
affects an air conditioner's performance. If the
air speed is too high, it will be noisy and
uncomfortable, and the return grille filter
effectiveness will be reduced. The speed through
the grilles depends on the size of the air
conditioner (a larger unit has more air flow and
higher air speed) and the area of the grille (a
smaller grille causes higher air speed).
With a properly
sized air conditioner, it is easier to have
sufficient supply and return grille area to keep
the air speed low and the noise at a minimum.
Common complaints about oversized air
conditioners are that they blast frigid air and
that they are noisy. A properly sized air
conditioner, with proper ductwork and grilles,
will provide longer cycles, more consistent
temperatures, and better mixing of the house air.
ACCA Manual D specifies a maximum return grille
velocity of less than 500 ft per minute and a
maximum supply outlet of less than 700 ft per
minute.
Figure 3 shows
that for a standard 2' x 2' return grille, the
500 ft per minute requirement is exceeded with
all units over 2 and one-half tons, with the
resulting increase in noise.
Most
Contractors Oversize
The submitted
calculations were all over the place (see Figure
4). In the extreme, the calculated load was three
times the Manual J calculated load.
Of the 40 load
calculations that were submitted, we approved
those that yielded building loads within 20% of
Manual J as received. This group included four
worksheets, one calculator method, and five
computer programs. The approval process was
interactive and led to many stimulating
conversations. David, a contractor for over 20
years, shared some of the "seat of the
pants" methods he had observed through the
years.
One method was
to "buy the distributor's overstock,"
another was to "install the rejected unit
from a previous job," and still another was
to "install the unit sitting in the truck or
at the shop." David referred to these
methods as "sizing by cost."
Contractors
submitted methods that they sincerely believed
would properly size air conditioners. Some of the
methods, however, were based on information from
as long ago as 40 years. These methods did not
take into account the latest efficiency
developments in building insulation, windows, and
air tightness.
The methods
were often handed down from the person who taught
them the business. "I learned this from my
father and it has always worked." Since the
contractors had received few or no complaints of
inadequate cooling, they considered their methods
sufficient. Unfortunately, they were
significantly oversizing units; particularly on
newer more energy-efficient homes. In an effort
to properly determine cooling load, some
contractors had spent good money on computer
programs, had developed their own methods from
books in the library, or borrowed from other
contractors in the area.
Manual J will
vary with the climate because of the way latent
loads are treated. Of the approved computer
methods, Right-J from Wrightsoft was the
most user friendly. Right-J from Wrightsoft
faithfully followed ACCA Manual J.
Many assumed
that the latent load was 30% of the sensible
load. The actual latent load is highly dependent
on the air tightness of the home, the local
climate, and the interior moisture sources (such
as people). For hot, dry climates, the latent
load will be far less than 30%, particularly if
the house has a large amount of air leakage from
the attic. For humid climates, the latent load
can be higher than 30% of the sensible load if
the house has a significant amount of air
leakage. In all cases, infiltration loads (air
leakage) were not specifically addressed or were
calculated by an oversimplified procedure.
Contractors often assumed that infiltration rates
were the same in all buildings or only depended
on floor area. With the widespread use of blower
door testing, we now know that homes vary
significantly in their leakage rate.
Don't Duck the
Duct Factor
The effect of
duct leakage has only recently been investigated
to any significant extent. As a result, cooling
loads due to duct leakage are not included in any
of the methods. Duct leakage has three effects on
design cooling load. First, a supply leak is a
direct loss in capacity. Second, a return leak
will often bring in superheated attic air. Third,
the difference between supply leakage and return
leakage will cause increased infiltration. While
it is tempting to treat duct leakage as
additional infiltration, the effect is actually
more complex.
How should the
loss due to duct leakage be taken into
consideration when an air conditioner is sized?
The answer of course is simple. Don't take duct
leakage into account - fix the leaksdegrees
Sizing by the
Square Foot
The
"square-foot-per-ton" sizing method
avoids calculating the cooling load of the
building and proceeds directly from the square
footage of the building to the size of the air
conditioner. No contractor submitted such a
method for approval but a number of contractors
reported that they often used this method, or
knew others who did. In a study by the Florida
Solar Energy Center, 25% of the contractors
reported that they size by floor area (see
"How They Size Air Conditioning Systems in
Florida," above).
While this
approach is rapid and simple, it does not account
for orientation of the walls and windows, the
difference in surface area between a one-story
and a two-story home of the same floor area, the
differences in insulation and air leakage between
different buildings, the number of occupants, and
many other factors. In some cases contractors
attempt to cover these variables by categorizing
the home as low (a new home in a moderate
climate), average, or high (an old home in a hot
climate) but this method also falls short of
properly sizing air conditioners.
Figure 5 was
produced with those types of categorizations.
Selecting
Equipment with Manual S
Manual J (or
other methods) gives a contractor both the
sensible and latent design loads for the house. A
common, but wrong, practice is to divide the
total cooling load by 12,000 Btu/h per ton and
choose an air conditioner with that nominal
tonnage. Nominal tonnage does not indicate
capacity under differing design conditions.
Manual S
provides a process for selecting equipment that
will meet the sensible and latent loads at Manual
J design conditions. Its primary strength is that
it guides the user to select an air conditioner
that has a sensible capacity between 100% and
115% of the calculated sensible load. This is a
major improvement over a number of other
methods. In dry climates the infiltrating
air carries less moisture into the house, the
indoor relative humidity is lower, and the latent
load is lower. With less moisture in the house
air, the air conditioner runs at a higher
sensible capacity.
Problems with
Manufacturer's Data
Air
conditioners selected based on standard indoor
conditions of 80 degrees F with 50% relative
humidity (which is the standard ARI capacity
rating condition) will be incorrectly sized for
75 degrees F. Unfortunately, many of the major
manufacturers provide information only at
80degreesF. It would be a great improvement if
the manufacturers provided tables that presented
the sensible and latent capacities at 75 degrees
F for a variety of indoor humidities.
|